- Wide range of output currents
- AC and DC voltage outputs
- All outputs continuously variable
- Output current metering from 40mA-200A
- Automatic switch-off in all modes of operation
- Multi-function timing system
- Suitable for testing thermal devices
- Compact and highly portable
- Voltage and current outputs available simultaneously
The 100A/E mk3 secondary current injection test set has been designed to give the maintenance and commissioning engineer a large number of facilities in one self-contained instrument.The unit is portable, compact and simple to use. The mains supply for the unit is either 240V±10% or 115V +10% -6% at either 50 or 60Hz. Full load can be obtained at the supply voltage extremes. The current and voltage outputs are independently controlled and metered. The output current and voltage are displayed on large, clear panel instruments. An additional four range CT is provided, extending the ammeter range down to 0-100mA.
All of the outputs are fully isolated by means of double wound transformers. The timing system on the 100A/E is very flexible, without compromising ease of use. Four modes of operation and two contact inputs are provided allowing for a wide range of events to be timed. Both contact inputs automatically select for normally open or normally closed contacts. Operation of the different timing modes is described overleaf.
Internal start mode starts the timer when the ‘ON’ pushbutton is pressed, and stops the timer when the first contact set changes state. This mode is ideally suited to timing over-current relays. Single contact mode starts and stops the timer on the first and second changes of state of the first contact set, and dual contact mode starts the timer from the first set of contacts and stops it from the second set. These modes allow reset and re-close times of protective devices to be easily measured.
The final mode of operation of the timer starts the timer when the current exceeds 20% of the selected metering range, and stops it when the current falls below 20%. This allows the timing of trips with no auxiliary contacts such as miniature circuit breakers. Automatic control has been provided such that all outputs can be switched off once the device under test has operated. The automatic control can be switched in or out of circuit for all outputs, enabling setting up procedures to be carried out. The instrument is housed in a robust case complete with a protective cover and fold-away carrying handles.
The current output on the unit has eight ranges, allowing the selection of output voltages up to 150V and output currents up to 200A. The voltage output on the unit has three ranges, allowing the selection of output voltages up to 500Vac and 250VDC. If using a 100ADM-F with the 100A/E mk 3 unit you will need to to order A0006-0010 lead set.
The output of the 100A/E mk3 secondary current injection test set is a true RMS analogue system with separate instruments for current and voltage. AC current is metered by a dual scaled ammeter reading 0-1A and 0-5A. AC voltage is metered by a dual scaled ammeter reading 0-300V and 0-600V. The output may be automatically switched off at the end of the test to safeguard the relay under test. This is available for both the voltage and current output.
Weight | 33 kg |
---|---|
Dimensions | 490 × 300 × 300 mm |
Supplied Accessories |
Operating manual |
Optional Accessories |
100ADM-F, Part no. 006 |